Features
• Adds I/o To J1939 Network
• Works With Standard J1939 Display Modules
• Wide Operating Temperature Range
• Industry Standard Deutsch Enclosure and Connectors
• Custom Programming Available
• Easy-to-Use Configuration Tool Available
Power Input: 8 to 32 VDC
Operating Temperature: -40 to 85°C (-40° to 185°F)
Digital Inputs: 4– Ground or battery positive activation
Digital Outputs*: 2 – Sinking (500 mA)
*(Outputs are NOT reverse polarity protected. Damage will occur if B+ is connected to the outputs. Damage incurred from improper installation is not covered under the FW Murphy limited warranty policy.)
Thermocouple Input1: Type K and Type J
Analog Inputs2:
• 1 – battery supply voltage (dedicated)
• 7 – configurable as 0-5 VDC, 4-20 mA, resistive senders3 or used as an additional Digital Input
Speed Sensing input: Magnetic Input (2 to 120 VAC RMS from 30 to 10,000 Hz.)
Communication Ports: CAN J1939
LED Indicators:
• PWR - Power On
• COP - Computer Operating Properly
• CAN - CANbus Active
Product Weight: 10 ounces
- Authorized Distributor
- Genuine Parts
- Service and Support
Electrical
- Power Input: 8 to 28VDC
- Communication Ports: CAN J1939
- Operating Temperature: -40°F to 185°F (-40°C to 85°C)
- Digital Inputs: 4 - Ground or battery positive activation
- Digital Outputs*: 2 Sinking (500 mA)
- Product Weight: 10 ounces
- Shipping Weight: 12 ounces
- Shipping Dimensions: 4” x 6” x 2”
*(Outputs are NOT reverse polarity protected. Damage will occur if B+ is connected to the outputs. Damage incurred from improper installation is not covered under the Murphy limited warranty policy.) - Thermocouple Input1: Type K and Type J
- Analog Inputs2:
- 1 - Battery Supply Voltage (dedicated)
- 7 - Configurable as 0-5VDC, 4-20mA, resistive senders3 or used as an additional digital input
- Speed Sensing Input: Magnetic pickup (2 to 120VAC RMS from 30 to 10,000 Hz)
1When the thermocouple input is used, only 5 resistive, 4-20 mA, or 0-5 VDC can be used instead of 7.
2Analog inputs can be exchanged for digital inputs (battery ground activation only) for a total of 11 digital inputs.
3Other resistive senders can be supported. Contact Murphy’s Industrial Panel Division for programming charges.